Generators

  • Air Cooled Gensets
  • R Series 20kVA to 82.5kVA
  • SL Series 180 kVA to 250 kVA
  • K Series 100kVA to 160 kVA
  • DV Series 320 kVA to 625 kVA

DG Set Specifications (15 to 70 kVA)

Parameters   Genset Model
  Unit KG15AS4 KG25AS-C KG30AS KG35AS KG40AS KG50AS KG70AS*
Prime Rating at 0.8 pf kVA (kW) 15 (12) 25 (20) 30 (24) 35 (28) 40 (32) 50 (40) 70 (56)
Voltage V 415 415 415 415 415 415 415
Frequency Hz 50 50 50 50 50 50 50
Overall Dimensions with canopy(L × W × H) mm 1770×1050×1550 2030×1050×1550 3130×1100×1680 3130×1100×1680 3220×1100×1680 3980×1240×1680 3980×1240×1680
Dry Weight of genset with canopy kg. 1220 1350 1440 1440 1580 1870 19 20
Electrical starting system Volt-DC 12 V 12 V 12 V 12 V 12 V 12 V 12 V
Battery Capacity Ah 88 88 100 100 100 120 120
DG set Noise level as per CPCB Norms dBA < 75 < 75 < 75 < 75 < 75 < 75 < 75

Engine Specifications

Parameters   Engine Model
  Unit HA294 SR3 HA394 HA494 HA494 HA494T HA694 HA694T
Rated output (prime rating as per ISO 3046) kW (hp) 15.08 (20.5) 23.5 (32) 331.6 (43) 31.6 (43) 41.2 (56) 47.8 (65) 61 (83)
No. of cylinder Nos. 2 3 4 4 4 6 6
Bore × Stroke mm 100 × 120 100 × 120 100 × 120 100 × 120 100 × 120 100 × 120 100 × 120
Aspiration NA NA NA NA T NA T
Governing Class as per ISO 3046 M3 M3 M3 M3 M3 M3 M3
SFC at 75% load* (g/Hp-hr) 168 170 159 159 166 161 169
SFC at 100% load* (g/Hp-hr) 172 174 163 163 166 161 165.5
Lub oil Consumption* LPH 0.01 0.02 0.02 0.02 0.03 0.03 0.035
Lub oil change period** hrs 500 500 500 500 500 500 500
Lub oil Sump capacity Ltrs 4.5 8 11 11 11 13.5 13.5

Alternator Specifications

Parameters   Alternator Model
  Unit KG164 J KG 184B KG 184D KG184D KG 184E KG 204D KG 224B
Rating kVA 15 20 30 35 40 50 70
Insulation Class H H H H H H H
Protection IP23 IP23 IP23 IP23 IP23 IP23 IP23
Time to built up rated voltage at rated RPM sec < 5 < 5 < 5 < 5 < 5 < 5 < 5
Alternator Efficiency at 75% load % 84.9 89.8 90.5 90.7 90.8 90.8 92.5
Alternator Efficiency at 100% load % 83.5 88.8 89 89.1 89.2 89.7 91.2
Voltage regulation % +1 +1 +1 +1 +1 +1 +1
Wave form Distortion at No load & at Non-distorting balanced linear Load % < 1.8 & < 4 < 1.8 & < 4 < 1.8 & < 4 < 1.8 & < 4 < 1.8 & < 4 < 1.8 & < 4 < 1.8 & < 4
Permissible transient voltage dip at full load 0.8 pf lag*** % < 18 < 18 < 18 < 18 < 18 < 18 < 18

In the view of continuous product updation and design changes, all above specifications & dimensions are subject to change without prior notice

Notes :

  • Genset ratings as per ISO 8528 performance class is G2.
  • Prime Power Rating is the maximum power available continuously for a variable electrical load for unlimited number of hours per year under standard operating conditions.
  • For the site conditions other than standard operating conditions, consult KOEL for available prime power.
  • All canopy dimensions have tolerance of + 50 mm.
  • **First oil change at 50 hours.
  • ***Permissible transient % voltage dip at full load 0.8 pf lag (alternator tested alone) as per IS 4722.
  • With 5% overload capacity.
  • *+5 % tolerance as per ISO 3046. For LPH calculation specific gravity of diesel is considered as 0.845.

DG Set Specifications (20 to 82.5 kVA)

Parameters   Genset Model
  Unit KG20WS4 KG25WS5 KG30WS KG40WS KG50WS KG62.5WS2 KG82.5WS2
Prime Rating at 0.8 pf kVA (kW) 15 (12) 25 (20) 30 (24) 35 (28) 40 (32) 50 (40) 70 (56)
Voltage V 415 415 415 415 415 415 415
Frequency Hz 50 50 50 50 50 50 50
Overall Dimensions with canopy(L × W × H) mm 2050×950×1220 2380×950×1230 2380×950×1230 2650×1050×1605 3350×1190×1650 3240×1140×1585 3240×1140×1585
Dry Weight of genset with canopy kg. 925 1100 1250 1520 1500 1900 1950
Electrical starting system Volt-DC 12 V 12 V 12 V 12 V 12 V 12 V 12 V
Battery Capacity Ah 1×88 1×88 1×88 1×100 1×100 1×100 1×100
DG set Noise level as per CPCB Norms dBA < 75 < 75 < 75 < 75 < 75 < 75 < 75

Engine Specifications

Parameters   Engine Model
  Unit 2R1040 3R1040 3R1040 4R1040 4R1190 4Rl040T 4Rl040TA
Rated output (prime rating as per ISO 3046) kW (hp) 20.6 (27) 30.9 (42) 30.9 (42) 41.2(56.1) 45.6 (62) 61 (83) 77.2(105)
No. of cylinder Nos. 2 3 3 4 4 4 4
Bore × Stroke mm 105x12O 105x12O 105x12O 105x12O 110x125 105x12O 105x12O
Aspiration NA NA NA NA NA T TA
Governing Class as per ISO 3046 M3 M3 M3 M3 M3 M3 M3
SFC at 75% load* (g/Hp-hr) 157 157 157 155 156 156 150
SFC at 100% load* (g/Hp-hr) 174.9 156 156 155 153 155 151
Lub oil Consumption* LPH 0.015 0.015 0.015 0.035 0.035 0.04 0.05
Lub oil change period** hrs 500 500 500 500 500 500 500
Lub oil Sump capacity Ltrs 4.5 7.5 7.5 9.5 9.5 9.5 9.5
Engine coolant capacity Ltrs 10 12 12 18 18 24 24

Alternator Specifications

Parameters   Alternator Model
  Unit KG 184A KG 184B KG 184C KG 184E KG 204D KG 224A KG 224D
Rating kVA 15 20 30 35 40 50 70
Insulation Class H H H H H H H
Protection IP23 IP23 IP23 IP23 IP23 IP23 IP23
Time to built up rated voltage at rated RPM sec < 5 < 5 < 5 < 5 < 5 < 5 < 5
Alternator Efficiency at 75% load % 88.5 89.8 90.5 90.8 90.8 91.8 92.5
Alternator Efficiency at 100% load % 87.1 88.8 89 89.2 89.7 91 91.4
Voltage regulation % 1% with 4% Engine Govering 1% with 4% Engine Govering 1% with 4% Engine Govering 1% with 4% Engine Govering 1% with 4% Engine Govering 1% with 4% Engine Govering 1% with 4% Engine Govering
Wave form Distortion at No load & at Non-distorting balanced linear Load % < 1.8 & < 4 < 1.8 & < 4 < 1.8 & < 4 < 1.8 & < 4 < 1.8 & < 4 < 1.8 & < 4 < 1.8 & < 4
Permissible transient voltage dip at full load 0.8 pf lag*** % < 18 < 18 < 18 < 18 < 18 < 18 < 18

In the view of continuous product updation and design changes, all above specifications & dimensions are subject to change without prior notice

Notes :

  • Genset ratings as per ISO 8528 performance class is G2.
  • Prime Power Rating is the maximum power available continuously for a variable electrical load for unlimited number of hours per year under standard operating conditions.
  • For the site conditions other than standard operating conditions, consult KOEL for available prime power.
  • *+5 % tolerance as per ISO 3046. For LPH calculation specific gravity of diesel is considered as 0.845.
  • All canopy dimensions have tolerance of + 50 mm.
  • **First oil change at 50 hours.
  • Single phase genset option available upto 40kVA.
  • ***Permissible transient % voltage dip at full load 0.8 pf lag (alternator tested alone) as per IS 4722.

DG Set Specifications (180 to 250 kVA)

Parameters   Genset Model
  Unit KG180WS2 KG200WS2 KG250WS1
Prime Rating at 0.8 pf kVA (kW) 180 (144) 200 (160) 250 (200)
Voltage V 415 415 415
Frequency Hz 50 50 50
Overall Dimensions with canopy(L × W × H) mm 4940×1700×2050 4940×1700×2050 4940×1700×2050
Dry Weight of genset with canopy kg. 3870 3950 4660
Electrical starting system Volt-DC 24× (2×12 V) 24× (2×12 V) 24× (2×12 V)
Battery Capacity Ah 2×160 2×160 2×180
DG set Noise level as per CPCB Norms dBA < 75 < 75 < 75

Engine Specifications

Parameters   Engine Model
  Unit 6SL1500TA SR1 6SL1500TA SR2 6SL8800TA
Rated output (prime rating as per ISO 3046) kW (hp) 164.8 (224) 184 (250) 228 (310)
No. of cylinder Nos. 6 6 6
Bore × Stroke mm 118 × 135 118 × 135 118 × 135
Aspiration TA TA TA
Governing Class Electronic A0 Electronic A0 Electronic A0
SFC at 75% load* (g/Hp-hr) 148 148 150
SFC at 100% load* (g/Hp-hr) 149 149 153
Lub oil Consumption* LPH 0.11 0.11 0.14
Lub oil change period** hrs 500 500 500
Lub oil Sump capacity Ltrs 24 24 24
Engine coolant capacity Ltrs 43 43 43

Alternator Specifications

Parameters   Alternator Model
  Unit KG 254 M0 KG 254 M1 KG 284 L1
Rating kVA 180 200 250
Insulation Class H H H
Protection IP23 IP23 IP23
Time to built up rated voltage at rated RPM sec < 5 < 5 < 5
Alternator Efficiency at 75% load % 93.6 93.9 93.9
Alternator Efficiency at 100% load % 93 93.5 93.6
Voltage regulation % 1% with 4% with Engine Governing 1% with 4% with Engine Governing 1% with 4% with Engine Governing
Wave form Distortion at No load & at Non-distorting balanced linear Load % < 1.8 & < 4 < 1.8 & < 4 < 1.8 & < 4
Permissible transient voltage dip at full load 0.8 pf lag*** % < 18 < 18 < 18

In the view of continuous product updation and design changes, all above specifications & dimensions are subject to change without prior notice

Notes :

  • Genset ratings as per ISO 8528 performance class is G3.
  • Prime Power Rating is the maximum power available continuously for a variable electrical load for unlimited number of hours per year under standard operating conditions.
  • For the site conditions other than standard operating conditions, consult KOEL for available prime power.
  • *+5 % tolerance as per ISO 3046. For LPH calculation specific gravity of diesel is considered as 0.845.
  • All canopy dimensions have tolerance of + 50 mm.
  • **First oil change at 50 hours.
  • ***Permissible transient % voltage dip at full load 0.8 pf lag (alternator tested alone) as per IS 4722.

DG Set Specifications (100 to 160 kVA)

Parameters   Genset Model
  Unit KG 100 WS KG 125 WS KG 140 WS2 KG 160 WS2
Prime Rating at 0.8 pf kVA (kW) 100 (80) 125 (100) 140 (112) 160 (128)
Voltage V 415 415 415 415
Frequency Hz 50 50 50 50
Overall Dimensions with canopy(L × W × H) mm 3200×1300×1805 3200×1300×1805 4040×1540×1900 4040×1540×1900
Dry Weight of genset with canopy (Aprox) kg. 925 2034 3500 3550
Electrical starting system Volt-DC 12 V 12 V 12 V 12 V
Battery Capacity Ah 1×120/130 1×120/130 1×150 1×150
DG set Noise level as per CPCB Norms dBA < 75 < 75 < 75 < 75

Engine Specifications

Parameters   Engine Model
  Unit 4K1080TA 4K1080TA1 6K1080TA SR1 6K1080TA
Rated output (prime rating as per ISO 3046) kW (hp) 92 (125) 114.7 (156) 127.4 (173) 147.2 (200)
No. of cylinder Nos. 4 4 6 6
Bore × Stroke mm 105x125 105x125 105x125 105x125
Aspiration TA TA TA TA
Governing Class Electronic A0 Electronic A0 Electronic A0 Electronic A0
SFC at 75% load* (g/Hp-hr) 150.5 146 146 146
SFC at 100% load* (g/Hp-hr) 151 146 146 146
Lub oil Consumption* LPH 0.065 0.07 0.085 0.09
Lub oil change period** hrs 500 500 500 500
Lub oil Sump capacity Ltrs 14.8 14.8 22 22
Engine coolant capacity Ltrs 28 28 35 35

Alternator Specifications

Parameters   Alternator Model
  Unit KG 224F KG 224H KG 254S0 KG 254S1
Rating kVA 100 125 140 160
Insulation Class H H H H
Protection IP23 IP23 IP23 IP23
Time to built up rated voltage at rated RPM sec < 5 < 5 < 5 < 5
Alternator Efficiency at 75% load % 92.8 93.2 93.2 93.3
Alternator Efficiency at 100% load % 92 92.6 92.6 92.8
Voltage regulation % 1% with 4% Engine Govering 1% with 4% Engine Govering 1% with 4% Engine Govering 1% with 4% Engine Govering
Wave form Distortion at No load & at Non-distorting balanced linear Load % < 1.8 & < 4 < 1.8 & < 4 < 1.8 & < 4 < 1.8 & < 4
Permissible transient voltage dip at full load 0.8 pf lag*** % < 18 < 18 < 18 < 18

In the view of continuous product updation and design changes, all above specifications & dimensions are subject to change without prior notice

Notes :

  • Genset ratings as per ISO 8528 performance class is G3.
  • Prime Power Rating is the maximum power available continuously for a variable electrical load for unlimited number of hours per year under standard operating conditions.
  • For the site conditions other than standard operating conditions, consult KOEL for available prime power.
  • *+5 % tolerance as per ISO 3046. For LPH calculation specific gravity of diesel is considered as 0.845.
  • All canopy dimensions have tolerance of + 50 mm.
  • **First oil change at 50 hours.
  • ***Permissible transient % voltage dip at full load 0.8 pf lag (alternator tested alone) as per IS 4722.

DG Set Specifications (320 to 625 kVA)

Parameters   Genset Model
  Unit KG320 WS4 KG380 WS KG 400 WS2 KG 500 WS3 KG 600 WS3 KG 625 WS3
Prime Rating at 0.8 pf kVA (kW) 320 (256) 380 (304) 400 (320) 500 (400) 600 (480) 625 (500)
Voltage V 415 415 415 415 415 415
Frequency Hz 50 50 50 50 50 50
Overall Dimensions with canopy(L × W × H) mm 5700×2000×2555 5700×2000×2555 5700×2000×2555 6200×2000×2555 6600×2000×2705 6600×2000×2705
Dry Weight of genset with canopy (Aprox) kg. 5200 6000 6000 6655 7500 7500
Electrical starting system Volt-DC 24 (2×12 V) 24 (2×12 V) 24 (2×12 V) 24 (2×12 V) 24 (2×12 V) 24 (2×12 V)
Battery Capacity Ah 180 180 180 180 180 180
DG set Noise level as per CPCB Norms dBA < 75 < 75 < 75 < 75 < 75 < 75

Engine Specifications

Parameters   Engine Model
  Unit DV6I TA SR1 DV8 SR2 DV8 DV10 DV12 DV12 SR1
Rated output (prime rating as per ISO 3046) kW (hp) 284 (386) 346 (470) 360 (490) 448(608) 532 (723) 552 (750)
No. of cylinder Nos. 6 8 8 10 12 12
Bore × Stroke mm 123x155 130x15O 130x15O 130x15O 130x15O 130x15O
Aspiration TA TA TA TA TA TA
Governing Class Electronic A0 Electronic A0 Electronic A0 Electronic A0 Electronic A0 Electronic A0
SFC at 75% load* (g/Hp-hr) 147 145 144 146 144 144
SFC at 100% load* (g/Hp-hr) 147 143 143 143 143 143
Lub oil Consumption* LPH 0.11 0.10 0.10 0.13 0.16 0.16
Lub oil change period** hrs 250 500 500 500 500 500
Lub oil Sump capacity Ltrs 23 41 41 45 50 50

Alternator Specifications

Parameters   Alternator Model
  Unit KG 284 C KG 354 S1 KG 354 S2 KG 354 M1 KG 354 L1 KG 354 L2
Rating kVA 320 380 400 500 600 625
Insulation Class H H H H H H
Protection IP IP23 IP23 IP23 IP23 IP23 IP23
Time to built up rated voltage at rated RPM sec < 5 < 5 < 5 < 5 < 5 < 5
Alternator Efficiency at 100% load % 93.8 94.1 94.1 94.8 95.5 95.5
Voltage regulation % +1 +1 +1 +1 +1 +1
Wave form Distortion at No load & at Non-distorting balanced linear Load % < 1.8 & < 4 < 1.8 & < 4 < 1.8 & < 4 < 1.8 & < 4 < 1.8 & < 4 < 1.8 & < 4
Permissible transient voltage dip at full load 0.8 pf lag*** % < 18 < 18 < 18 < 18 < 18 < 18

In the view of continuous product updation and design changes, all above specifications & dimensions are subject to change without prior notice

Notes :

  • Genset ratings as per ISO 8528 performance class is G3.
  • Prime Power Rating is the maximum power available continuously for a variable electrical load for unlimited number of hours per year under standard operating conditions.
  • For the site conditions other than standard operating conditions, consult KOEL for available prime power.
  • *+5 % tolerance as per ISO 3046. For LPH calculation specific gravity of diesel is considered as 0.845.
  • All canopy dimensions have tolerance of + 50 mm.
  • **First oil change at 50 hours.
  • ***Permissible transient % voltage dip at full load 0.8 pf lag (alternator tested alone) as per IS 4722.